BCAB #1202
April 18, 1990
Re: 1 - 9.34.2.7. - Floor Protection for Heating Appliance (Stove)
2 - 9.23.12.4. & 9.23.12.5. - Lintel in Exterior Wall
3 - 9.8.8. & 9.8.9.5. - Exterior stairs for Single Family Dwelling
4 - 9.21.6.1. - Clearances for Masonry Chimney
5 - 9.12.2.2. & 9.12.2.4. - Depth of Foundations
Project Description
Single family dwelling of wood frame construction. Five items are appealed.
- Reason for Appeal #1202 - 1
- The floor surface beneath and surrounding a solid fuel fired stove or space heater must be noncombustible.
- Appellant's Position
- The noncombustible hearth to extend 16" in front of the stove.
- Building Official's Position
- The noncombustible surface must extend 450 mm (18") in front of the stove.
- Appeal Board Decision #1202 - 1
- Article 9.34.2.7. applies and requires the floor beneath the stove to be protected
by a noncombustible pad conforming to Articles 9.34.2.8. to 9.34.2.11.
(noncombustible) extending 450 mm (18") beyond the firing and ash removal
sides of the appliance and 200 mm (8") beyond the other sides. The 16" hearth
shown in the supplied sketch is not acceptable.
* * * * * * * * * * * * * * *
-
Reason for Appeal #1202 - 2
- Lintels are required over openings in load bearing walls.
- Appellant's Position
- Existing 3 - 2" x 6" lintel is adequate over a 6' opening.
- Building Official's Position
- The Code calls for a greater depth of lintel in Table 9.23.12.A.
- Appeal Board Decision #1202 - 2
- Part 9 of the Building Code can be described as "prescriptive" because it
prescribes methods of construction that are considered safe. This approach
allows buildings to be constructed without the services of design professionals
such as structural engineers or Architects. The trade-off is that the Code does
not consider the actual loads acting on each structure but rather envisions the
worst case. As long as the prescriptive requirements are followed there is no
problem.
Since you have chosen not to follow the prescriptive requirements laid down in
the Code you must be prepared to prove to the satisfaction of the
building inspector that the method of construction chosen is equal to, or better
than, that prescribed by the Code. The building inspector may require that you
provide engineered calculations to verify your design.
* * * * * * * * * * * * * * *
-
Reason for Appeal #1202 - 3
- Disagreement over safety requirements for exterior stairs.
- Appellant's Position
- Intermediate "safety rails" on stair guard/handrail can be parallel to the handrail;
and that exterior treads do not require non-skid finish.
- Building Official's Position
- The stair handrail to be minimum 800 mm high and the treads must have a slip-resistant finish. Original request that "safety rails" be vertical so as to be
nonclimbable was rescinded.
- Appeal Board Decision #1202 - 3
- The Code does not require the intermediate "safety rails" to be vertical.
Subsection 9.8.8. does not require nonclimbable guards for stairs serving
residential dwelling units. Article 9.8.9.5. requires treads and landings of exterior
stairs serving dwellings to have a slip-resistant finish or be provided with slip-resistant strips.
* * * * * * * * * * * * * * *
-
Reason for Appeal #1202 - 4
- Clearance is required between combustible materials and masonry chimneys.
- Appellant's Position
- Roof sheathing be permitted within 1/2" of chimney.
- Building Official's Position
- Interior chimneys require a clearance of 2" to combustible materials including
sheathing.
- Appeal Board Decision #1202 - 4
- The Board considers this to be an interior chimney passing through an attic
space and terminating above the roof surface. Article 9.21.6.1. requires
combustible materials, including sheathing to be not less than 50 mm (2") from
the chimney. However, the Board does not consider a 12 mm clearance to the
sheathing to be a hazard and is recommending that the Code be revised to
permit this construction and to clarify its application to other interior/exterior
installations.
* * * * * * * * * * * * * * *
-
Reason for Appeal #1202 - 5
- Subsection 9.12.2. stipulates the minimum depth of foundations below finished
ground level.
- Appellant's Position
- The appellant feels that an 18" minimum foundation depth is acceptable.
- Building Official's Position
- The local officials have established 24" as a reasonable minimum depth considering the wide variety in local conditions but will accept less if it can be shown a
lesser depth will be satisfactory.
- Appeal Board Decision #1202 - 5
- It is not the function of the Board to determine or maintain records of minimum
foundation depth requirements throughout the Province. Article 9.12.2.4. allows
the authority having jurisdiction to permit foundation depths less than stipulated
in Table 9.12.2.A. if local experience shows lesser depths to be satisfactory. We
agree with the building official that you must demonstrate that a depth less than
24" is satisfactory for any specific location.
George R. Humphrey, Chair
Return to Index