Project Description
The project under appeal is the plumbing drainage system in a one storey office building.
Reason for Appeal (revised)
This appeal concerns connecting water closets to a circuit vented system, the location of a relief vent in a circuit vented system containing a nominally horizontal offset and the use of a wet vent as a circuit vent.
Appellant's Position
The appellant contends the following:
Plumbing Official's Position
The plumbing official maintains that water closet arms must be installed as per the requirements for Special Waste Systems as noted in the Appendix A-4.2.1.(4). The plumbing official states that the B.C. Plumbing Code permits a circuit vent to be sized as a wet vent but must be installed in accordance with dry vents as required in the 1985 B.C. Plumbing Code.
It is the determination of the Board that the three items under appeal in this drainage system do not contravene any specific requirements of the B.C. Plumbing Code.
George R. Humphrey, Chair